MGC-95093B
Revised 03-00
Catalog Section 75
(00-02-0134)
FRANK W.
MFR.
Generator Panel
MGC921 Series
I
Available in Manual or Auto Start
– 12 or 24 VDC Battery Voltage
– Single Phase or 3-Phase
I
I
Compact
Full Featured
I Manual Start Panel includes the
following features.
Description
Specifications
The MGC921 provides economical engine and
generator control for applications not requiring
NFPA-99 or NFPA-110 approval. Models are
available for Manual or Automatic start designed
for 3-phase, 4-wire or 1-phase, 3-wire genera-
tors. Models MGC921 feature mechanical
SWICHGAGE®s for engine oil and coolant tem-
perature. Models MGC921E feature EGS elec-
tric SWICHGAGE®s. The panels are housed in a
13 x 10 x 11 in. (330 x 254 x 279 mm) shock
mounted NEMA 1 drip-proof enclosure. Current
transformers (CT’s) are not included.
I Auto-Start Panel
•
Power OFF-ON toggle switch and start
push button.
•
Power Requirements:
– 12 VDC battery for 12 V models.
– 24 VDC battery for 24 V models.
•
•
518APH TATTLETALE® annunciator.
•
•
Inputs: Ground or positive inputs for high
temperature or low pressure sensors.
Auxiliary starter relay. Contact rating: 12 volt,
40 amp/24 volt 16 amp.
Oil Pressure SWICHGAGE®, 2 in (51 mm)
dial, 0-100 psi (0-689 kPa) [6.89 bar].
Temperature SWICHGAGE®, 2 in (51 mm)
dial, 130-250°F (54-121°C), 12 ft. (3.7 m)
capillary.
Outputs:
•
•
– Auxiliary starter relay. Contact rating:
12 volt, 40 amp/24 volt 16 amp.
– 300 mA transistors for fault annunciation
•
•
•
•
Operating Temperature: -4 to 140°F (-20 to
60°C).
•
Two (2) 2-1/16 in. (52 mm) diameter holes,
plugged.
Cycle Crank Timer: Up to 8 attempts.
Recrank on false starts (fixed 30 seconds).
Features
I Auto-Start Panel includes the following features.
I AC meters
Crank/Rest Cycle Timing: 4 to 25 seconds
(adjustable).
•
ASM150, auto-start controller with:
– Optically-isolated noise resistant inputs.
– Outputs for fault annunciator.
•
•
•
•
AC voltmeter, 3-1/2 in. (89 mm) dial, ±2%
full scale (specify range: 300 V or 600 V).
Shutdown Time Delay: 1 to 25 seconds
(adjustable). Locks out low oil pressure and
high temperature on start up.
AC ammeter, 3-1/2 in. (89 mm) dial, ±2%
full scale (specify range: 50 to 4000 A).
– Crank/rest cycle timer, 4 to 25 sec. adjustable.
– Shutdown time delay, 1 to 25 seconds
(adjustable), locks out low oil pressure
and high temperature on start-up.
– Crank disconnect and overspeed
sensing operates from a magnetic pickup
signal (requires 2 Vrms minimum).
AC frequency meter, 120 V, 3-1/2 in. (89
mm) dial, ±0.6% Hz, 45–65 Hz.
•
•
Crank Disconnect Speed Setting:
From 30 to 8500 Hz.
Frequency meter rheostat.
Overspeed Trip Point Setting:
From 30 to 8500 Hz.
Options
•
Magnetic Pickup Input:
I AC ammeter-voltmeter phase selector switch*.
•
•
•
Auxiliary starter relay. Contact rating: 12 volt,
40 amp/24 volt 16 amp.
Oil pressure SWICHGAGE®, 2-1/16 in. (52
mm) dial, 0-100 psi (0-689 kPa) [6.89 bar].
Temperature SWICHGAGE®, 2-1/16 in (52
mm) dial, 130-250°F (54-121°C), 12 ft.
(3.7 m) capillary.
Requires 2 Vrms minimum.
Requires 2 additional CTs.
I Manual Start Panel
I Hourmeter, 2 in. (51 mm) dial, 5-digit.
•
Power Requirements:
I Battery voltmeter, 2 in (51 mm) dial (range
determined by battery voltage).
– 12 VDC battery for 12 V models.
– 24 VDC battery for 24 V models.
I Battery ammeter, 2 in (51 mm), 60-0-60.
•
Operating Temperature: -4 to 140°F
(-20 to 60°C).
•
•
TEST-OFF-AUTO selector switch.
*Standard (included) with 3-phase models.
Two 2-1/16 in. (52 mm) dia. holes, plugged.
|
Miele Microwave Oven M 8151 2 User Manual
MTX Audio Speaker T4515 04 User Manual
National Geographic Thermometer 277 NE User Manual
NEC Flat Panel Television P60XP10 BK User Manual
Oki Network Card VK2000 User Manual
Omega Marine Instruments DPG5000 User Manual
Panasonic Impact Driver EY7542 User Manual
Panasonic Network Card 2SA1790J User Manual
Panasonic Telephone DBS 576HD User Manual
Paradyne Modem 316x User Manual